SNMP MIB for PDU outelet on/off

You can use the OID .1.3.6.1.4.1.17420.1.2.9.1.13 to control the PDU. The argument 1 means to turn on the outlet The argument 0 means to turn off the outlet The argument 5 means unchanging outlet status Example: Circuit 1 Get OID .1.3.6.1.4.1.17420.1.2.9.1.13 If PDU respond 1,1,1,1,1,1,1,1 means outlet A~H are power on If PDU respond 0,1,1,1,1,1,1,1 means outletA is power off, the other outlets are power on Set OID .1.3.6.1.4.1.17420.1.2.9.1.13, Send 1,1,1,1,0,0,0,0 means to turn on outletA~D, turn off outletE~H Send 1,5,5,5,5,5,5,5 means to only turn on outletA, the other outlets have not action. Circuit 2 Get OID .1.3.6.1.4.1.17420.1.2.9.2.13 If PDU respond 0,0,0,0,0,0,0,1 means outlet

POM PDU MIB for Control and Monitor

To get POM individual outlet current information by SNMP, please use OID as following .1.3.6.1.4.1.17420.1.2.9.1.11 .1.3.6.1.4.1.17420.1.2.9.2.11 .1.3.6.1.4.1.17420.1.2.9.3.11 .1.3.6.1.4.1.17420.1.2.9.4.11 .1.3.6.1.4.1.17420.1.2.9.5.11 .1.3.6.1.4.1.17420.1.2.9.6.11 .1.3.6.1.4.1.17420.1.2.9.7.11 .1.3.6.1.4.1.17420.1.2.9.8.11 or .1.3.6.1.4.1.17420.1.2.6.0 To set POM each outlet on/off by SNMP, please use OID as following .1.3.6.1.4.1.17420.1.2.9.1.13 .1.3.6.1.4.1.17420.1.2.9.2.13 .1.3.6.1.4.1.17420.1.2.9.3.13 .1.3.6.1.4.1.17420.1.2.9.4.13 .1.3.6.1.4.1.17420.1.2.9.5.13 .1.3.6.1.4.1.17420.1.2.9.6.13 .1.3.6.1.4.1.17420.1.2.9.7.13 .1.3.6.1.4.1.17420.1.2.9.8.13 To Get and Set the word before first

NPS Application

NPS Application Customer: System Integrator Problem 現有機櫃內的排插為基本型,無法提供耗電量的資訊,但客戶卻希望能夠對於機房運作影響最低的情況下,建立用電資訊監控。而預算也是考慮的重點。 Existing Basic PDU is basic type and unable to be monitored for the power consumption. Customer hopes to establish the power monitor system but the effect for operation will have the lowest situation. The budget is also the consideration key point. Solution 我們提供2埠式數位排插,此型的數位排插,可提供每一輸出埠的電源資訊,並具有控制,排程等附加控制功能;配合附贈的網路監控軟體,客戶可以在免拆除現有基本型排插的條件下,監視所有排插用電資訊。 DGP provides 2 port type PDU, this PDU can provide power information for each output port, and has the control, schedule control functions. To coordinate with free bundle network monitoring software, the customer can monitor all

Category
Featured Posts
Recent Posts
Archive
Search By Tags
Follow Us
  • Facebook Basic Square
  • LinkedIn Social Icon

9F.-7, No.75, Sec. 1, Xintai 5th Rd., Xizhi Dist., New Taipei City, Taiwan

Tel: +886-2-2698-8618  

Fax: +886-2698-8610

sales@digipower.com.tw

  • Facebook Clean
  • White LinkedIn Icon

© 2020 by Digipower Manufacturing Inc.